Hot Gas Reheat Dehumidification
|
Installed in |
 |
Models 52PE/PQ |
| Size |
Total
Cooling BTUH *
230/208 Volt |
SHR |
EER |
Latent
BTUH |
Sensible
BTUH |
| 07 |
6,800/6,600 |
.62 |
11.6 |
2584 |
4216 |
| 09 |
8,500/8,400 |
.58 |
11.0 |
3570 |
4930 |
| 12 |
11,200/11,000 |
.61 |
10.5 |
4368 |
6832 |
| 15 |
14,000/13,800 |
.62 |
9.2 |
5320 |
8680 |
* Rated in accordance with ARI Standard 310/380-2004 at
conditions of 95 F DB 75 F WB outdoors and 80 F 67 F WB indoors.
Notes:
- BTUH = BTU per Hour
- EER = Energy Efficiency
Ratio (BTU per Watt)
- SHR = Sensible Heat Ratio
- Latent Heat = BTU per
Hour - the energy of the unit being used to dehumidify the air in the indoor
area.
The average latent BTUF capacities for Carrier PTAC or PTHP (Heat Pumps)
with Dehumid IItm is 40% of the total BTUH of the unit.
For most, if not all standard major brand PTAC units, the average latent
heat is 30% of the total BTUH.
Technical Data - Carrier 52P Premier Series PTAC's